CP 343-1 Advanced SIMATIC NET 6GK7343-1GX31-0XE0

CP 343-1 Advanced SIMATIC NET 6GK7343-1GX31-0XE0

Communications processor CP 343-1 Advanced for connection of SIMATIC S7-300 CPU to Industrial Ethernet: PROFINET IO controller a./o. IO device; RT and IRT, MRP, PROFINET CBA; TCP/IP, ISO, UDP, S7 comm., S5-compat. communication (SEND/RECEIVE) with Fetch/Write RFC1006, Multicast Diagnostic extension, SNMP, DHCP, FTP client/server, e-mail, Gigabit-SS1X RJ45 (10/100/1000) PROFINET interface 2x RJ45 (10/100 Mbit); PROFINET CBA; security (firewall/VPN); PROFIenergy

6GK7343-1GX31-0XE0 là mô đun mở rộng truyền thông cho PLC S7-300 (CPU) do hãng SIEMENS phát triển & sản xuất với thương hiệu SIMATIC thuộc họ S7-300. CP 343-1 Advanced SIMATIC NET 6GK7343-1GX31-0XE0 được SIEMENSIM.COM phát triển và phân phối rộng rãi trên thị trường Việt Nam. Nếu quý khách hàng đang có nhu cầu cần tư vấn hay mua 6GK7343-1GX31-0XE0 thì hãy liên hệ SIEMENS INDUSTRY MALL để được hỗ trợ một cách tận tâm, nhanh chóng và hiệu quả nhé.

Tóm tắt thông số kỹ thuật 6GK7343-1GX31-0XE0

Mã sản phẩm 6GK7343-1GX31-0XE0
Dòng sản phẩm SIMATIC S7-300, CP 343-1 Advanced
Hãng sản xuất SIEMENS
Truyền thông RJ45 (10/100/1000)

RJ45 (10/100 Mbit)

Nguồn cung cấp Nguồn ngoài: 24 VDC

Nguồn từ backplane bus: 5 VDC

Kích thước (RxCxS) 80x125x120 mm
Trọng lượng 800 g

Chi tiết thông số kỹ thuật 6GK7343-1GX31-0XE0

Tải về datasheet (pdf): Tại đây!

transfer rate
transfer rate
● at the 1st interface 10 … 1000 Mbit/s
● at the 2nd interface 10 … 100 Mbit/s
interfaces
number of interfaces / acc. to Industrial Ethernet 3
number of electrical connections
● at the 1st interface / acc. to Industrial Ethernet 1
● at the 2nd interface / acc. to Industrial Ethernet 2
● for power supply 1
type of electrical connection
● at the 1st interface / acc. to Industrial Ethernet RJ45 port
● at the 2nd interface / acc. to Industrial Ethernet RJ45 port
type of electrical connection
● for power supply 2-pole plugable terminal block
design of the removable storage
● C-PLUG Yes
supply voltage, current consumption, power loss
type of voltage / of the supply voltage DC
supply voltage / 1 / from backplane bus 5 V
supply voltage / external 24 V
supply voltage / external / at DC / rated value 24 V
relative positive tolerance / at DC / at 24 V 20 %
relative negative tolerance / at DC / at 24 V 15 %
consumed current
● from backplane bus / at DC / at 5 V / typical 0.14 A
● from external supply voltage / at DC / at 24 V / typical 0.48 A
● from external supply voltage / at DC / at 24 V / maximum 0.62 A
power loss [W] 14.7 W
ambient conditions
ambient temperature
● for vertical installation / during operation 0 … 40 °C
● for horizontally arranged busbars / during operation 0 … 60 °C
● during storage -40 … +70 °C
● during transport -40 … +70 °C
relative humidity
● at 25 °C / without condensation / during operation / maximum 95 %
protection class IP IP20
design, dimensions and weights
module format Compact module
width 80 mm
height 125 mm
depth 120 mm
net weight 0.8 kg
fastening method
● S7-300 rail mounting Yes
performance data / open communication
number of possible connections / for open communication / by means of SEND/RECEIVE blocks / maximum 16
data volume
● as user data per ISO connection / for open communication / by means of SEND/RECEIVE blocks / maximum 8 Kibyte
● as user data per ISO on TCP connection / for open communication / by means of SEND/RECEIVE blocks / maximum 8 Kibyte
● as user data per TCP connection / for open communication / by means of SEND/RECEIVE blocks / maximum 8 Kibyte
● as user data per UDP connection / for open IE communication / by means of SEND/RECEIVE blocks / maximum 2 Kibyte
number of Multicast stations 16
performance data / S7 communication
number of possible connections / for S7 communication
● maximum 16
performance data / multi-protocol mode
number of active connections / with multi-protocol mode 48
performance data / IT functions
number of possible connections
● as client / by means of FTP / maximum 10
● as server / by means of FTP / maximum 2
number of possible connections
● as server / by means of HTTP / maximum 4
● as email client / maximum 1
data volume / as user data for email / maximum 8 Kibyte
storage capacity / of the user memory
● as flash memory file system 28 Mibyte
● as RAM 30 Mibyte
number of possible write cycles / of the flash memory cells 100000
performance data / PROFINET communication / as PN IO controller
product function / PROFINET IO controller Yes
number of PN IO devices / on PROFINET IO controller / operable / total 128
number of PN IO IRT devices / on PROFINET IO controller / operable 128
number of external PN IO lines / with PROFINET / per rack 1
data volume
● as user data for input variables / as PROFINET IO controller / maximum 4 Kibyte
● as user data for output variables / as PROFINET IO controller / maximum 4 Kibyte
● as user data for input variables per PN IO device / as PROFINET IO controller / maximum 1433 byte
● as user data for output variables per PN IO device / as PROFINET IO controller / maximum 1433 byte
● as user data for input variables per PN IO device / for each sub-module as PROFINET IO controller / maximum 240 byte
● as user data for output variables per PN IO device / for each sub-module as PROFINET IO controller / maximum 240 byte
performance data / PROFINET communication / as PN IO device
product function / PROFINET IO device Yes
data volume
● as user data for input variables / as PROFINET IO device / maximum 1024 byte
● as user data for output variables / as PROFINET IO device / maximum 1024 byte
● as user data for input variables / for each sub-module as PROFINET IO device 240 byte
● as user data for output variables / for each sub-module as PROFINET IO device 240 byte
● as user data for the consistency area for each sub-module 240 byte
number of submodules / per PROFINET IO-Device 32
performance data / PROFINET CBA
number of remote connection partners / with PROFINET CBA 64
number of connections / with PROFINET CBA / total 1000
data volume
● as user data for digital inputs / with PROFINET CBA / maximum 8 Kibyte
● as user data for digital outputs / with PROFINET CBA / maximum 8 Kibyte
● as user data for arrays and data types / in the case of acyclic transmission / with PROFINET CBA / maximum 8 Kibyte
● as user data for arrays and data types / with PROFINET CBA / with cyclical transfer / maximum 250 byte
● as user data for arrays and data types / with PROFINET CBA / in the case of local interconnection / maximum 2400 byte
performance data / PROFINET CBA / remote interconnection / with acyclic transfer
update time / of the remote interconnections / in the case of acyclic transmission / with PROFINET CBA 100 ms
number of remote connections to input variables / in the case of acyclic transmission / with PROFINET CBA / maximum 128
number of remote connections to output variables / in the case of acyclic transmission / with PROFINET CBA / maximum 128
data volume
● as user data for remote interconnections with input variables / in the case of acyclic transmission / with PROFINET CBA 8 Kibyte
● as user data for remote interconnections with output variables / in the case of acyclic transmission / with PROFINET CBA 8 Kibyte
performance data / PROFINET CBA / remote interconnection / with cyclic transfer
update time / of the remote interconnections / with PROFINET CBA / with cyclical transfer 8 ms
number of remote connections to input variables / with PROFINET CBA / with cyclical transfer / maximum 200
number of remote connections to output variables / with PROFINET CBA / with cyclical transfer / maximum 200
data volume
● as user data for remote interconnections with input variables / with PROFINET CBA / with cyclical transfer / maximum 2000 byte
● as user data for remote interconnections with output variables / with PROFINET CBA / with cyclical transfer / maximum 2000 byte
performance data / PROFINET CBA / HMI variables via PROFINET / acyclic
number of connectable HMI stations / for HMI variables / in the case of acyclic transmission / with PROFINET CBA 3
update time / of the HMI variables / in the case of acyclic transmission / with PROFINET CBA 500 ms
number of HMI variables / in the case of acyclic transmission / with PROFINET CBA / maximum 200
data volume / as user data for HMI variables / in the case of acyclic transmission / with PROFINET CBA / maximum 8 Kibyte
performance data / PROFINET CBA / device-internal interconnections
number of internal connections / with PROFINET CBA / maximum 256
data volume / of the internal connections / with PROFINET CBA / maximum 2400 byte
performance data / PROFINET CBA / interconnections to constants
number of connections with constants / with PROFINET CBA / maximum 200
data volume / as user data for interconnections with constants / with PROFINET CBA / maximum 4096 byte
performance data / PROFINET CBA / PROFIBUS proxy functionality
product function / with PROFINET CBA / PROFIBUS proxy functionality No
performance data / telecontrol
protocol / is supported
● TCP/IP Yes
product functions / management, configuration, engineering
product function / MIB support Yes
protocol / is supported
● SNMP v1 Yes
● SNMP v3 Yes
● DCP Yes
● LLDP Yes
configuration software
● required STEP7 V5.5 SP2 HF1 or higher / STEP 7 Professional V12 (TIA Portal) or higher
● for PROFINET CBA / required SIMATIC iMap V3.0 SP4 and higher
identification & maintenance function
● I&M0 – device-specific information Yes
● I&M1 – higher level designation/location designation Yes
product functions / diagnostics
product function / web-based diagnostics Yes
product functions / switch
product feature / switch Yes
product function
● switch-managed No
● with IRT / PROFINET IO switch Yes
● configuration with STEP 7 Yes
product functions / redundancy
product function
● ring redundancy Yes
● redundancy manager Yes
protocol / is supported / Media Redundancy Protocol (MRP) Yes
product functions / security
firewall version stateful inspection
product function / with VPN connection IPSec
type of encryption algorithms / with VPN connection AES-256, AES-192, AES-128, 3DES-168, DES-56
type of authentication procedure / with VPN connection Preshared key (PSK), X.509v3 certificates
type of hashing algorithms / with VPN connection MD5, SHA-1
number of possible connections / with VPN connection 32
product function
● password protection for Web applications Yes
● ACL – IP-based Yes
● ACL – IP-based for PLC/routing Yes
● switch-off of non-required services Yes
● blocking of communication via physical ports Yes
● log file for unauthorized access No
product functions / time
product function / SICLOCK support Yes
product function / pass on time synchronization Yes
protocol / is supported
● NTP Yes
standards, specifications, approvals / hazardous environments
certificate of suitability / CCC / for hazardous zone according to GB standard Yes

Phân phối và báo giá 6GK7343-1GX31-0XE0

Nếu quý khách hàng đang có nhu cầu cần tư vấn hay mua 6GK7343-1GX31-0XE0 thì hãy liên hệ SIEMENS INDUSTRY MALL để được hỗ trợ một cách tận tâm, nhanh chóng và hiệu quả nhé.

Danh mục: Module truyền thông S7-300, SIMATIC S7-300
Để lại một bình luận